PLATE HEAT EXCHANGER CALCULATION - SWEP 97.11 *
**************************************************************
*** DESIGN CALCULATION - GC-26
***
Customer: Date:
2000/7/4
:------------------------------------------------------------:
: Duty
requirements :
:------------------------------------------------------------:
Side 1 Side 2
Inlet temperature
C : 56.00 33.00
Outlet temperature
C : 48.00 43.00
Flow
rate kg/h : 78000 62343
Max.
pressure drop mwc : 5.00 5.00
Number of heat transfer units
NTU : 0.572 0.716
:------------------------------------------------------------:
: Physical
properties :
:------------------------------------------------------------:
Fluid number
: 1 1
Fluid name
: Water Water
Reference temperature
C : 52.00 38.00
Viscosity cP : 0.528 0.680
Viscosity - wall
cP : 0.550 0.641
Density
kg/m3 : 985.9 991.6
Specific heat capacity
kcal/kg,C : 0.997 0.998
Thermal conductivity
kcal/m,h,C : 0.554 0.540
:------------------------------------------------------------:
: Plate heat exchanger :
:------------------------------------------------------------:
Heat
load Mcal/h : 622.0
Total heat transfer area
m2 : 31.72
Log
mean temperature difference C : 13.98
Overall H.T.C.
kcal/m2,h,C :
3182/1403
Calculated pressure drop
mwc : 1.38 0.91
Number of channels
: 62H 61H
Connection diameter
mm : 100 100
Total number of plates :
124
Oversurfacing
% : 127
Fouling factor
m2,h,C/Mcal :
0.398