* PLATE HEAT EXCHANGER CALCULATION - SWEP 97-11
**************************************************************
*** DESIGN
CALCULATION - GC-26 ***
Customer: Date:2000/7/4
:
------------------------------------------------------------:
: Duty requirements :
:------------------------------------------------------------:
Side 1 Side 2
Inlet temperature
C : 56.00 33.00
Outlet temperature
C : 48.00 43.00
Flow
rate kg/h : 78000 62343
Max.
pressure drop mwc : 5.00 5.00
Number of heat transfer units
NTU : 0.572 0.716
:------------------------------------------------------------:
: Physical
properties :
:------------------------------------------------------------:
Fluid number
: 1 1
Fluid name
: Water Water
Reference temperature
C : 52.00 38.00
Viscosity cP : 0.528 0.680
Viscosity - wall
cP : 0.576 0.605
Density
kg/m3 : 985.9 991.6
Specific heat capacity
kcal/kg,C : 0.997 0.998
Thermal conductivity
kcal/m,h,C : 0.554 0.540
:------------------------------------------------------------:
: Plate heat exchanger :
:------------------------------------------------------------:
Heat
load Mcal/h : 622.0
Total heat transfer area
m2 : 7.80
Log
mean temperature difference C : 13.98
Overall H.T.C.
kcal/m2,h,C :
5648/5706
Calculated pressure drop
mwc : 5.03 3.72
Number of channels
: 16MH 15ML
Connection diameter
mm : 100 100
Total number of plates :
32